Technical FAQs

Ask a Question

What is the difference between a CAFI and a DF breaker?

Issue:
What is the difference in a CAFI Combination Arc Fault Circuit Breaker and a DF Dual Function breaker?

Product Line:
Circuit Breakers

Environment:
UL 489, CSA 22.2 No. 5, NOM/ANCE and NEMA AB1, Federal Specification W-C-375B/GEN, NFPA 70

Cause:
The 2014 National Electrical Code adds new locations for which arc fault protection is required, and the new requirement may overlap with locations where ground fault circuit interruption is required as well.

Resolution:
Combination Arc Fault Circuit Interrupters protect branch circuits and all downstream receptacles and cord sets against both high-energy parallel arcing (the same as existing branch/feeder AFCIs) and low-energy series arcing. A Dual Function Device combines Combination Arc Fault Protection with Class A Ground fault (People) protection.

For more information on Square D QO™ Combination Arc Fault Circuit Interrupters, click here.

For more information on Square D HomeLine™ Combination Arc Fault Circuit Interrupters, click here.

Dual Function Devices meet 2014 National Electrical Code requirements and combine two state-of-the-art technologies; Combination Arc Fault and Ground Fault protection, in a single, easy-to-install device.

For more information on Square D QO™ Dual Function Circuit Breakers, click here.

For more information on Square D HomeLine™ Dual Function Circuit Breakers, click here.
 
Was this helpful?
What can we do to improve the information ?