What is the difference between the LA36400 and LC36400 being used at 480 Vac?


Product Line:
Legacy Circuit Breakers
I Line

Environment:
Electrical Distribution Equipment

Resolution:
The LA is rated at 480 v 30 KAIC and the LC at 480 v is 65 KAIC and also LA needs 6 inches of mounting space and LC needs 7.5 inches of mounting space.
 