How do you calculate the maximum possible Available Fault Current at the secondary for single-phase and three-phase Transformers?
Issue:
Transformer Available Fault Current

Product Line
LV Transformers

Environment:
Applies to LV single phase and three phase Transformers by SquareD/Schneider Electric

Cause:
Transformers are often connected to equipment that is rated for certain AIC, Average Interrupting Current, or Available Fault Current

Resolution:
Take the secondary full load current of the Transformer and divide it by the Transformer`s impedance. This is not necessary on Transformers below 15kVA, thus why UL does not require the impedance on the nameplate of Transformers below 15kVA.

For example, a three phase 75kVA Transformer with a 208Y/120 V secondary and 5% impedance has a capacity of 208 amps (three-phase formula is I=kVA/1.732*V) on the secondary. The peak let through with an infinite source (worst case scenario) would have 208 / 0.05 = 4,160 amps of peak let through current (available fault current).

Now, a single phase 75kVA Transformer with a 120 V secondary and 5% impedance has a capacity of 625 amps (single-phase formula is I=kVA/V) on the secondary. The peak let through with an infinite source (worst case scenario) would have 625 / 0.05 = 12,500 amps of peak let through current (available fault current).

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.