What is the difference between a 80% rated breaker and a 100% rated breaker?

Issue:
What is the difference between a 80% rated breaker and a 100% rated breaker?
Do we have a list of 100% rated circuit breakers?

Product Line:
Molded case circuit breakers

Environment:
Electical disribution systems

Cause:
Need application information

Resolution:
For a particular breaker, even though the 80% and 100% versions have the same amp rating (use the same trip curve), in actual use they are applied differently depending on the continuous loads (amount and length of time).

The 80% (standard-rated) breaker can only be applied continuously (defined as 3 hours or more by the NEC) at 80% of its continuous current rating. 100% rated circuit breakers can be applied at up to 100% of their current rating continuously.  Breakers rated at 80% can be applied at 100% of their rating if the loading will last for less than 3 hours.

The following frames have versions that can be 100% rated:
  • Powerpact H frame:  unit mounted only,  with special suffix
  • Powerpact J frame:  unit mounted only,  with special suffix
  • Powerpact L frame:  Unit mounted or ILINE up to 400 amps, with special suffix
  • Powerpact P and R frame, with special suffix
  • Masterpact NT and NW
For further information, see the attached link:
http://blog.schneider-electric.com/datacenter/power-and-cooling/2014/06/12/clearing-confusion-80-vs-100-rated-circuit-breakers/

 