What type of fuses are required in Square D/Schneider Electric`s Industrial Control Transformers 9070 Type T w/ field installed 9070FB fuse block or Type TF (factory installed fuse block)?

Issue:
Fuses are needed to install in the Fuse Blocks of some 9070 Class Control Transformers

Product Line:
LV Control Transformers

Environment:
Applies to Fused Control Transformers by SquareD/Schneider Electric

Cause:
Fuse Blocks for 9070 Class Control Transformers are not supplied with fuses from the factory


Resolution:

Two Class CC fuses (time delay, rejection type) are needed on the primary, and one midget (11/32`` x 1-1/2``)  fuse is needed on the secondary


 