What is the Terminal Lug Data for ALL of the 800amp, heavy duty safety switches (for example, H367, H367R or H367AWK)?

Issue:
Product Design Features

Product Line:
Heavy Dutye Safety Switch

Cause:
Terminal lug data

Resolution:

ALL the 800amp Heavy Duty Safety Switches will accept (3) #3/0 AWG - 750 kcmil aluminum or copper conductors per phase. The only alternate lugs are compression lugs.

 