Will the C60 Vigi module work with the C60N UL489 circuit breakers?

Issue:
Are the C60N UL489 breaker compatible with C60  Vigi module?
 
Product Line:
Circuit Breaker

Environment:
Multi-9 Circuit Breaker
 
Resolution:
No. It will work only with the UL1077 and IEC versions.
 