What is the AL1200P24K lug kit data for Powerpact M, P frame breakers?

Published date: 20 August 2019

Product Line:
Circuit Breakers
PowerPact M and P

Environment:
Electrical Distribution Equipment

Resolution:
Conductor:        Al/Cu
Lugs per kit:      1
Construction:     I-LINE M and P frame breakers, Individually-mounted M frame breakers.
Conductors:       4
Size:                 3/0 - 500 kcmil
Strip length:       1.2 in.

Torque:
Wire binding screw torque:     442.5 lb-in
Lug mounting screw torque:   190 lb-in

NOTE:
Tool required: Screwdriver, POZIDRIV #2 or #3, or slotted. Socket Wrench, 7mm hex (for wire binding screw). Torque Wrench, 5/16 in. or 8mm.
 