What terminations are available on a 225A NQOD neutral assembly?

Issue:
What is the wire size and quantity of terminations for the neutral assembly for the NQOD 225A panel board?

Product Line:
panelboard, panel

Environment:
NQOD

Resolution:
Main Lug:
Aluminum = (1) #6 - 300MCM
Copper = (1) #6 - 250MCM

*Note 1 additional lug may be added to accept a larger conductor:
QO70AN =  (1) # 10 - #2 AL or #14 - #4 CU
QO1100AN = (1) #4 - 1/0 AL or CU
QO150AN =  (1) # 1 - 4/0 AL or CU

Branches:
(45) #4 - 14





 