What are the replacement lugs for EDB, EGB, EJB, FDA, FGA, and FJA breakers?

Issue:
What are the replacement lugs for EDB, EGB, EJB, FDA, FGA, and FJA breakers?

Product Line:
I-Line Panels, NF Panels, FA frame breakers, E-Frame Breakers

Environment:
Panelboards and Molded Case Circuit Breakers

Cause:
Need to replace existing lugs

Resolution:
 Cat #  Amp  Wire Range  Instruction Bulletin
 AL30FD  15-30A  one #12—#6 AWG Al or one #14—#6 AWG Cu 48840-098-02
 AL100FD  35-125A  one #12—2/0 AWG Al or one #14—2/0 AWG Cu
 CU100FD  15-125A  one #14—1/0 AWG Cu

Notes
  • In the standard 15-30A EDB, EGB, and EJB breakers, high amp lugs can be factory installed with suffix LH. If they are not ordered factory installed, standard high amp lug kit AL100FD CANNOT be used on the 15-30A breakers. Copper high amp lug kit CU100FD can still be used even if the breaker was not ordered with high amp lugs.
  • Each lug kit contains (3) lugs.