What is the standard lug kit for FA breakers?

Issue:
What lugs come as standard on FA breakers

Product Line:
Circuit Breakers

Environment:
Legacy FA Breakers

Cause:
Application

Resolution:
FA breakers from 15A to 30A: AL50FA  - accepts (1) 14-4 AWG copper or (1) 12-4 AWG aluminum 
FA breakers from  35A to 100A:  AL100FA - accepts (1) 14-1/0 AWG copper or (1) 12-1/0 AWG aluminum

Note: AL50FA may be used as optional lugs for 35A to 100A FA breakers and;
AL100FA may be used as optional lugs for 15A to 30A FA breakers