Do we have lugs for an LAL breaker which will accept 2-350kcmil conductors?

Published date: 10 June 2019

Product Line:
Legacy Circuit Breaker

Environment:
Electrical Distribution Equipment

Resolution:
We do not offer a mechanical lug option. Maximum size for (2) conductors is 250 kcmil for Mechanical Lug.
However, the optional compression lug kit VC400LA35 will accept (2) 250kcmil to 350kcmil.
 