What are the voltage amperage ratings for the built-in auxiliary contacts and LADN__ or LAD8N__ auxiliary contact modules for the D-Line contactors?

Issue:
Does the built-in auxiliary contacts and LADN__ or LAD8N__ auxiliary contact have VA ratings?

Product Line:
Tesys D line Contactors and Accessories

Environment:
IEC TeSys D Contactor Accessories

Resolution:
Auxiliary contacts are rated A600 for AC voltages and P600 for DC voltages as shown below:
A600 is rated 10 amp maximum continuous carrying current with maximum make volt-amp rating of 7200 VA and maximum break volt-amp rating of 720 VA.
P600 is rated 5 amp maximum continuous carrying current with maximum make/break volt-amp rating of 138VA.

Maximum make and break current rating as listed below:

Volts Make Break
120 vac 60.0 6.0
240 vac 30.0 3.0
480 vac 15.0 1.5
600 vac 12.0 1.2

125 vdc 1.1 1.1
250 vdc 0.55 0.55
301-600 vdc 0.20 0.20


 