What is the Terminal Lug Data for ALL of the 200amp, Heavy Duty Safety Switches (for example; a HU364A, H364, H364DS and H364AWK)?

Issue:

Product Design Features

Product Line:
Heavy Dutye Safety Switch

Cause:
Terminal lug data

Resolution:
The 200amp Heavy Duty Safety Switches will accept (1) #6 AWG - 250 kcmil aluminum or copper conductors per phase. With the following exceptions:
The H225XJG and H225XJGAA will ONLY use 75 degree Copper wire and accept (1) #3 AWG - 350Kcmil. These are NOT UL listed due to inadequate wire bending space (5" for ON end and 6" for OFF end)

NOTE: The only alternate lugs are compression lugs, BUT they do NOT change the size or quantity as mentioned above.




 