What size of Allen (hex head) wrench is required for the main lug wire binding screws on a 150, 200 or 225 ampere Main Lug QO or HOMELINE load center?

Issue:
Wiring details

Product Line:
QO and HOM LC

Cause:
Torque requirement

Resolution:
The lugs on these Main Lug load centers use a 3/8`` Allen (hex head) wrench and should be torqued to 250 Lb-In. 