Is there a transformer that can take a single phase input and create a three phase output?

Issue:
Can a single phase transformer create a three phase output?

Product Line:
Transformers

Environment:
Low voltage Transformers

Resolution:
It is not possible to change a single phase source into a three phase source with a static device, such as a transformer. An active device is required, examples of which are phase converters or some special variable frequency drives. 