Is a circuit breaker rated per pole or total?

Issue:
Is a circuit breaker rated per pole or total?

Product Line:
Circuit Breakers

Resolution:
Each pole is rated for the specified amps and the breaker is rated the same amperage total. For example, a 3p, 600 A breaker is rated 600 A at each pole, but is also rated 600 A total, not 1800 A.