What is the Terminal Lug Data for ALL of the 400amp, Heavy Duty Safety Switches (For example, HU365RB, H365, H365AWK and H365DS)?

Issue:

Product Design Features

Product Line:
Heavy Dutye Safety Switch

Cause:
Terminal lug data

Resolution:

The 400amp Heavy Duty Safety Switches will accept (1) 1/0 AWG - 750 kcmil Al/Cu OR (2) 1/0-300kcmil Al/Cu conductors per phase. With the exception of the following;
Maximum wire bending space for the Type 4/4X/5 Stainless Steel and Type 12 Switches will allow for (1) 600kmcil Al/Cu or (2) 300kcmil Al/Cu conductors per phase.

NOTE: The only alternate lugs are compression lugs and they do NOT allow for any different wire size or quantity than what is shown above.




 