| FA168145 | On an E-Flex, what is modification B09? This option provides a line contactor factory wired between the circuit breaker disconnect ( or line reactor when provided ) and the ATV61 power converter.... |
| FA168120 | What type of enclosure is the MD3304X? The enclosure is Non-metallic, rated for both indoor and outdoor use, is UV and corrosion resistant (Types 1, 3, 3R, 4, 4X, and 12). See the Instruction... |
| FA168118 | Are the Subway service fittings for the trench duct available? No. The Subway product line and the service fittings are no longer available. Refer to page 14-1 of the Supplemental & Obsolescence Digest 174 for... |
| FA168126 | Is the LDGB wireway available? No. LDB wireway is only available in a painted steel enclosure.
CTA-ID : 2062909 |
| FA168127 | Is the LDB wireway available in a galvanized housing? No. LDB wireway is only available in a painted steel enclosure.
CTA-ID : 2062908 |
| FA91969 | Can voltage be continuously applied to shunt trip devices for Powerpact HD, HG, HJ, HL, and HR circuit breakers? Yes, all Powerpact shunt trip accessories are continuous duty rated. CTA-ID : 2055503 |
| FA110477 | What is wire range for the LAL tenant breaker used in the EZML111400? The LAL tenant breaker will accept (1) #1 AWG to 600KCMIL or (2) #1 AWG to 250 KCMIL per phase as standard. CTA-ID : 2019901 |
| FA118301 | What is the part number for the QMB circuit breaker adapter unit that accepts the Powerpact J frame breaker? QMBJW. Use a S37445 J frame breaker nut insert kit with this . CTA-ID : 2030443 |
| FA167794 | How much smaller horsepower motor, can I put a ATV drive? Rule of Thumb for smaller horsepower motors. The drive horsepower is higher than the motor horsepower.
We recommend typically not going lower than... |
| FA167795 | ATV61 / 71 . Can I use a temperature sensor to control the drive speed? No, the drive uses analog inputs. Temperature sensor output will need to be converted to voltage, current or a contact transistion (preset speed)... |