Results 1 - 4 of 4
1
FAQ ID
Description
FA130608
(TEN FIFTY B)
25098606 Ten Fifty B, line item 183 & 184 busway runs
Customer contacted the FO 02-24-10 reporting a problem with RCTB clearance at the job site, stating that the actual tap box dimensions differ from those shown on the approval drawings. They would like a solution from Square D.
Oxford redesigned the RCTBs to a smaller dimension so that they satisfied the clearance requirements. Field Services removed the original RCTBs and...
FA117579
9012G or 9016G in NEMA 4 enclosure. Cover screw for the corner where the cover chain attaches is not long enough to secure the cover.
Contact Raleigh PSGCTA-ID : 2029296
FA102269
Powerpact R frame top stabs are firm. Bottom stabs have small wriggle 1/8 in from front to back. Is this small amount of wriggle normal?
A small amount of movement on the bottom terminals is normal. CTA-ID : 2007161
FA89134
Did we make a change to the ring nut that holds on the knob on the 9001 K selector switches? Customers are getting mixed units in shipments.
Yes. They are plastic now. CTA-ID : 5153