Can you install a QO240GFI, QO250GFI or QO260GFI breaker in a QO24L70RB load center?
When using a QO GFI branch breaker, the QO24L70F, S or RB has adequate wire bending space for a maximum #10 AWG wire. This will normally restrict the QO GFI breaker to a maximum of 30 amperes.
CTA-ID : 15514
CTA-ID : 15514
Answers which others found helpful |