Can I get ground fault trip on a Masterpact NT/NW and then turn it off later?
No. To disable ground fault, you would need to replace the trip unit.
CTA-ID : 2007247
FA102526 |
14-Jan-2011
|
Product Features
PDF
Email
Bookmark
Print
Answers which others found helpful
> Customer has a Masterpact breaker with an electronic trip unit which includes ground fault. They do not want ground fault. Can it be turned off?
> Customer has a Masterpact NT, which includes ground fault. They do not want ground fault. Can it be turned off?
> We are attempting to understand the implications of using LF or L1F arc flash NW`s in a selectively coodinated system. If we need to turn the Instantaneous OFF to coordinate, are we disabling the arc flash limiting properties of the NW?