What is the termination temperature rating of a QO breaker?

Issue:
What is the temperture rating for a QO breaker termination?

Product Line:
QO, QOB

Resolution:
QO breakers rated 10 to 30 A, as well as electronic breakers, are suitable for use with 60 deg C or 75 deg C wire. QO breakers rated 35 to 125 A are rated for use with 75 deg C wire only.