Are the fuse clips replaceable on I Line Busplugs?

Can Fuse clips  and Fuse bases be replaced in I Line  Busplugs ?
Product Line:

Maintenance and replairs parts are often needed and being to get fuse clips and fuse base replacements for I Line Busplugs may become necessary . Knowing the amperage, Series , is necessary in deternmining if parts are available

Replacement Load base fuse bases and clips are available for replacement for the following Series Switches :
PQ (30-100A) Series 004
PQ (200A) Series 006
PS (200) Series 005
PBQ (400A & 600A) Series 006

Only the LOAD fuse base assembly is replaceable on these plug-in unit. The line side fuse clips are not field replaceable.

Load Bases for 800A thru 1600A fusible plug in units are not available