What do you look for when trouble shooting a QO120GFI?

The first things to check are:
neutral wire must run to GFI breaker - not the neutral bar,
neutral must not to be grounded downstream of the GFI breaker,
neutral must not used as a common neutral,
wire run not to exceeds 250 feet one way.