What is the maximum temperature that a Mini Power-Zone enclosure surface can reach?

The maximum allowable surface temperature rise above ambient for a Mini Power-Zone (MPZ) is a 65degC.  With maximum ambient temperature of 40degC, the surface of the MPZ could reach 105degC (221degF.)  Remember the 24 hour average ambient should not exceed 30degC (86degF.)


CTA-ID : 2003059