Can a HOM30L200C load center be converted to a Main Breaker device?

The answer is dependent upon the Series number of the HOM30L200C. Series 1 and Series 2 were considered ``fixed Main Lugs`` and not convertible to Main Breaker. A Series S01 device may be converted to a Main Breaker by using a QOM2100VH (100 amp) through QOM2200VH (200 amp) Main Circuit Breaker Kit. A QOM2200VH would be the maximum Main Breaker allowed.