Technical FAQs

Ask a Question

Does the rating plug need to be removed for hi-pot or dielectric testing on breakers with the basic and ``A`` trip units?

No. But it is necessary to remove the rating plug on the ``P`` or ``H`` trip units.


CTA-ID : 2001886
Was this helpful?
What can we do to improve the information ?