Technical FAQs

Ask a Question

What are the acceptable wire sizes and torque values for the GV1G09 and GV2G05?

Product Line:
 
GV Manual Motor Starters and Protectors
 
Resolution:
 Solid cable:
(1) #14 to #2 AWG conductor or
(2) #14 to #6 AWG conductors

Flexible cable without cabel end:
(1) #14 to #2 AWG conductor or
(2) #12 to #6 AWG conductors

Flexible cable with cabel end:
(1) #14 to #4 AWG conductor or
(2) #14 to #10 AWG conductors

Tightening Torque:
Connector = 20 lb-in
Screw Clamp = 15 lb-in

 
Was this helpful?
What can we do to improve the information ?