Are there any recommendations concerning the cleaning of a QO or Homeline load center interior?

Issue:
Maintenance Instructions

Product Line:
QO and Homeline Load centers

Resolution:

For general cleaning, disconnect all power feeding the load center and remove the branch circuit breakers from the panel interior. Use a vacuum to remove any lose dirt or dust from the interior. Wipe down the interior with a dry, lint free cloth. Do not use any petroleum based products. Allowing petroleum base paint, solvents or spray to contact the non-metallic parts of this product may adversely affect user safety and impair reliability.


CTA-ID : 2002039