Masterpact NW with Micrologic 6.0A trip unit and is doing primary injection testing on it. Asking if he can disable ground fault in order to perform testing.

Use the Hand Held Test Kit, Cat. No. S33594 , or use the looping method to counter the single phase current during primary injection testing. See the attached Data Bulletin 0600DB9901 page 35, for looping method, or FAQ FA265488.