Is there a way to set an Electronic Trip Breaker to respond as an Thermal Magnetic Breaker?

Yes. A table is provided on pg. 22 of Doc# 0602CT9201R11/97 which shows the `Trip Unit Settings to Approximate Thermal Magnetic Circuit Breakers`. This table demonstrates how to do so.