What is the recommended torque for the joint bolt of an I-Line busway once the outer head of the Visi-Tite bolt has been twisted off?

The recommended torque for the joint bolts of I-Line busway is 70 lb-ft +/-10 lb-ft. The torque on the bolt should only be checked with the busway de-energized.