What is the magnetic (instantaneous) multiplier to determine the equivalent DC trip range for the KA/KH ac breaker?

The multiplier is 1.15 for the high setting, 1.3 for the low setting.   See data bulletin 0100DB0101 for complete details on rerating for direct current.