What is the torque for the MLO lug set-screw and lug bolt 1000A HCW2353-12?

Lug set screw - 340 in/lbs.

1/2`` KEPS nut w/ al terminals:  #2 - 600MCM CU-AL (1/2`` socket) - 38 ft lbs.

1/2`` KEPS nut w/ cu terminals:  #2 - 600MCM CU-AL (3/8`` socket) - 25 ft lbs.

This information is listed in document PN119.  