Is a QO breaker rated to accept 2 conductors under 1 terminal ?

Issue:
How many wires can be put in the terminal of a 10A - 30A QO circuit breaker?

Product Line:
Circuit Breakers

Environment:
Applies to QO and QOB, 1-, 2- and 3-poles, 10A through 30A
Does not apply to QOT breakers.
Does not apply to breakers with suffix GFI, AFI, CAFI, DF, EPD, or EPE

Resolution:
Yes, QO breakers (10-30A) are rated to accept 2 conductors under 1 terminal for copper wire size #14-#10.
The breakers are also rated to accept 1 conductor for wire size #14-#8 Cu or Al.