Do EDB, EGB, or EJB circuit breakers have a DC voltage rating?

Issue:  
Need to know if NF panels are appropriate for usage on DC applications

Product line:  
Molded case circuit breakers for use in NF panelboards

Environment:  
Powerpact EDB, EGB, and EJB circuit breakers

Resolution:  
The EDB, EGB, and EJB breakers do not have any DC ratings.  Use an NQ panel for applications up to 48 Vdc or an I-line panel for applications up to 250 Vdc.  