Technical FAQs

Ask a Question

Is a neutral CT needed for ground fault summing on a MX36800G?

An external neutral CT is necessary only for a 4-wire system that is using a micrologic breaker with ground fault.


CTA-ID : 15974
Was this helpful?
What can we do to improve the information ?