Can a HOM240GFI or HOM250GFI branch breaker be used in the HOM24L70F, HOM24L70S and HOM24L70RB load center?

Issue:
Product features

Product Line:
Homeline load centers

Environment:
branch breakers

Cause:
Application

Resolution:

No, When using a HOM-GFI branch breaker, the HOM24L70F, S or RB has adequate wire bending space for a maximum #10 AWG wire. This will normally restrict the HOM-GFI breaker to a maximum of 30 amperes.