Can the HOM240GFI or HOM250GFI breaker be installed in the HOM24L70S load center?

Issue:
product design features

Product Line:
Homeline load centers

Cause:
Application

Resolution:
When using a HOM-GFI branch breaker, the HOM24L70F, S or RB has adequate wire bending space for a maximum #10 AWG wire. This will normally restrict the HOM-GFI breaker to a maximum of 30 amperes.