Can a QO240GFI, QO250GFI or QO260GFI branch breaker be used in a QO24L70F, QO24L70S, QO2L40RB, QO24L70RB load center?

Issue:
Product features

Product Line:
QO load centers

Environment:
branch breakers

Cause:
Application

Resolution:

No, When using a QO-GFI branch breaker, the QO2L40RB, QO24L70F, S or RB has adequate wire bending space for a maximum #10 AWG wire. This will normally restrict the QO-GFI breaker to a maximum of 30 amperes.

CTA-ID : 15514