What is the difference between a PQ4620G and PS4620G fusible plug-in unit ?

Issue:
Application of Busplugs

Product Line:
Busway

Environment:
I-Line

Cause:
Selection

Resolution:
The PQ4620G is designed to be used on busway that is running horizontally, such as in a factory. A PS4620G is to be used when the busway is running vertically ( only mount on the rightside), such as in a multi story building..