Technical FAQs

Ask a Question

How can I charge an NW breaker when it is out of the cell? The handle is free and the charge indicator says ``discharged.``

Charge NW breaker when racked out of cell

Product Line:
Circuit Breakers
Masterpact NW

Electrical Distribution Equipment

Need to charge handle while breaker is out of cell or out of service.

You need the metal key that comes with the breaker to defeat the interlock. The key rotates the half-moon metal shaft on the upper left side of the breaker, and slips under the black crank.

For additional information see instruction bulletin HRB28631 in our technical library.

Technical Library:

CTA-ID : 14431
Was this helpful?
What can we do to improve the information ?