How would you tie an existing digital speed meter from and 8804 that is retrofitting to the new ATV66 drive?

Program the AO of the ATV66 for frequency output and tie the common to the negative side of the meter and the analog output terminal of drive to the positive side of meter and shunt across a 125 ohm resistor.