Are QO load centers suitable for use on a 48V dc application?

Issue:
Product design features

Product Line:
QO singe phase load centers

Environment:
Voltage ratings

Cause:
Application

Resolution:
The load center catalog numbers listed below are UL LISTED, File E6294, for use on 48 V dc systems. The load centers labeling will NOT be MARKED showing the DC voltage system, however they are suitable for the application. QO branch breakers, 10-70 ampere (1 and 2 pole) are also UL LISTED for use on 48V dc systems. Short circuit current rating is limited to 5,000 amperes when used on 48V dc.
QO24L70F, S or RB
QO612L100F, S, DF, DS, DFCU, DSCU, RB, TRB or RBCU
QO816L100F, S, DF, DS, DFCU, DSCU, RB or RBCU
QO112L125G or GRB
QO11224L125G or GRB
QO116L125G
QO11624L125G or GRB
QO120L125G
QO12024L125G
QO124L125G or GRB
QO12030L150G
QO124L150G
QO130L150G or GRB
QO112L200G or GRB
QO130L200G or GRB
QO13040L200G or GRB
QO142L225G or QO142L225GRB



CTA-ID : 12412