What Class of fuse does the D224N, D224NRB, D324N and D324NRB general duty safety switches accept?

Issue:
Product design features

Product Line:
General Duty Safety Switches

Environment:
Fuses

Cause:
Installation

Resolution:

These switches accepts Class H or K fuses as standard. For current design Series F01, options include Class R fuses (field install Class R Fuse Kit HRK1020) and Class J fuses (field modify switch by moving the load base assemblies to altenate position marked in the enclosure). With Class H or K fuses installed, the switch is UL listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and HRK1020 fuse kit installed) or Class J fuses, the switch is UL listed for use on systems with up to 100,000 RMS Symmetrical Amperes available fault current.

NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability and will void the warranty.