Should a ground fault circuit breaker be used on a high-resistance ground (or ungrounded) system?

Can circuit breakers with ground fault protection be applied on a high resistance ground system?

Product Line:
Circuit Breakers

Ground Fault Circuit Breakers

Ground fault circuit breakers can be used on solidly-grounded systems, but what about resistance-grounded systems.

Ground fault circuit breakers are for use on solidly-grounded systems only. If the system is high resistance to ground (or an ungrounded system), the amount of ground fault current may not be sufficient to trip a ground fault breaker.