Do we use a smaller NEMA size Start contactor than the Run starter in our 8606 reduced voltage starters?

It depends on the NEMA size of the RVAT.  NEMA sizes 2 through 4 have the same size Start contactors as the Run starter.  Size 5 RVAT uses size 4 Start contactors and a size 5 Run starter;  size 6 RVAT uses size 5 Start contactors and a size 6 Run starter; etc.