Can I use a key interlock on a vertically mounted main breaker in a I-Line panelboard?

No. All I-Line key interlocked breakers must be located backfed in the branch breaker location. A special mounting bracket is used to mount the interlock. There isn`t a location for this bracket with a vertically mounted main breaker application.