Technical FAQs

Ask a Question

Does the new Micrologic< trip system meet ANSI standard C37.90.2 for radiated electromagnetic interference.

NO. The ANSI standard calls for 35 volts per meter for radiation susceptibility. The Micrologic< trip system is tested to 10 volts per meter.


CTA-ID : 9768
Was this helpful?
What can we do to improve the information ?