Does the new Micrologic< trip system meet ANSI standard C37.90.2 for radiated electromagnetic interference.

NO. The ANSI standard calls for 35 volts per meter for radiation susceptibility. The Micrologic< trip system is tested to 10 volts per meter.

CTA-ID : 9768